Hydronic Manifold Sizing & GPM Flow Calculator
Determine manifold port count, loop balancing, GPM flow rate, and circulator pump sizing. Loops are auto-balanced within 10% length variance to prevent hydraulic short-circuiting.
Quick Room Presets
Start from a common project size, then customize.
System-Wide Settings
Apply to all rooms/zones.
Rooms / Zones (1)
Cabinets, vanities, showers, islands — don't run PEX under these.
Current: 28 BTU/sq ft
Hydronic System Summary
Estimate only: These results are planning estimates, not a stamped engineering design or a Manual J heat-loss calculation. Have a licensed HVAC or plumbing contractor confirm loads and loop layout, and get permits where your local code official requires them.
Assumptions, units & code references
- Heat loss uses a typical BTU/hr per sq ft value for the insulation level you choose.
- Flow is based on that load and the design temperature drop (15 °F by default).
- Loop lengths include the run to the manifold and a 10% allowance, and each loop stays under the maximum length for the PEX size.
Units: Square feet (sq ft), BTU per hour (BTU/hr), feet of tubing (ft), gallons per minute (GPM), degrees Fahrenheit (°F).
Code references: Hydronic piping is covered by your locally adopted mechanical and plumbing codes, not the National Electrical Code. Circulators, zone actuators and thermostats still need wiring that meets the NEC edition your area enforces.
Equipment Checklist
Buyer-ready shopping list with exact quantities. Click any item to check current pricing on Amazon.
Disclosure: HeatedFloorCalc earns a commission if you buy through the links below, at no extra cost to you. As an Amazon Associate we earn from qualifying purchases. Products are matched to your calculated specs; check the manufacturer’s data before buying.
What this manifold calculator does
This tool helps you size a US hydronic radiant manifold. Enter each room, spacing, PEX size, and the distance to the manifold. It counts loops per room, adds them to get port count, computes system GPM from the heat load and ΔT, and warns if the longest and shortest loops differ by more than 10% of the longest loop.
The formula
Ports equal the total loop count. Loop length is (field ÷ loops + 2 × distance) × 1.1, with loops chosen so that length stays under 300 ft for 1/2 inch PEX or 200 ft for 3/8 inch. GPM = total BTU/hr ÷ (500 × ΔT). If (longest − shortest) / longest is over 10%, the tool shows a balancing warning.
Worked two-room example
Room A is 400 sq ft at 8 inch spacing, 20 ft from the manifold. Room B is 200 sq ft at 8 inch, also 20 ft away. Both use 1/2 inch PEX, 28 BTU/sq ft, and a 20°F ΔT. The calculator returns 3 loops at 264 ft in Room A, 2 loops at 209 ft in Room B, 5 manifold ports, 1,210 ft of PEX, and 1.7 GPM. Loop lengths vary by 21%, so the tool warns you to use balancing valves or adjust loop counts.
Read how to size a hydronic manifold for the full walkthrough, and radiant floor loop length for the 300 ft and 200 ft caps.
As an Amazon Associate I earn from qualifying purchases.
Frequently asked questions
- How many ports does the two-room example need?
- Five: 3 loops in the 400 sq ft room and 2 loops in the 200 sq ft room. Ports equal loops on this site.
- Why does this example show a balancing warning?
- The longest loop is 264 ft and the shortest is 209 ft, a 21% difference. The warning appears when that gap is more than 10% of the longest loop.
- What GPM does the example use?
- 16,800 BTU/hr at a 20°F ΔT is 1.7 GPM in the calculator (1.68 rounded to one decimal).
- Should I buy spare ports?
- Optional. The calculator sizes ports from the current loop count. A spare port is useful if you expect to add a room later.