Radiant Heat Loss & Boiler/Heat Pump Sizing Calculator

Estimate room-by-room BTU/hr heat loss using insulation presets (20, 28, or 35 BTU/sq ft) or a custom override. Subtract fixed obstacles and size your boiler or heat pump with GPM flow rate.

Quick Room Presets

Start from a common project size, then customize.

System-Wide Settings

Apply to all rooms/zones.

Rooms / Zones (1)

1

Cabinets, vanities, showers, islands — don't run PEX under these.

Net Heated Area100 sq ft

Current: 28 BTU/sq ft

This room:1 loop209 ft/loop210 ft PEX

Hydronic System Summary

Net Heated Area
100sq ft
Total Heat Load
2,800BTU/hr
Total PEX Tubing
210ft
Required Flow
0.4GPM
Loops
1
Per Loop
209ft
Manifold Ports
1
PEX Rolls
1×300ft
Balanced Loops — all loops are within 10% length variance and under the 300 ft max per loop. No hydraulic short-circuiting risk.

Estimate only: These results are planning estimates, not a stamped engineering design or a Manual J heat-loss calculation. Have a licensed HVAC or plumbing contractor confirm loads and loop layout, and get permits where your local code official requires them.

Assumptions, units & code references
  • Heat loss uses a typical BTU/hr per sq ft value for the insulation level you choose.
  • Flow is based on that load and the design temperature drop (15 °F by default).
  • Loop lengths include the run to the manifold and a 10% allowance, and each loop stays under the maximum length for the PEX size.

Units: Square feet (sq ft), BTU per hour (BTU/hr), feet of tubing (ft), gallons per minute (GPM), degrees Fahrenheit (°F).

Code references: Hydronic piping is covered by your locally adopted mechanical and plumbing codes, not the National Electrical Code. Circulators, zone actuators and thermostats still need wiring that meets the NEC edition your area enforces.

Equipment Checklist

Buyer-ready shopping list with exact quantities. Click any item to check current pricing on Amazon.

Disclosure: HeatedFloorCalc earns a commission if you buy through the links below, at no extra cost to you. As an Amazon Associate we earn from qualifying purchases. Products are matched to your calculated specs; check the manufacturer’s data before buying.

1
1/2" Oxygen-Barrier PEX Tubing
1 × 300 ft coil (210 ft total incl. 10% waste). Zero underground splices.
Why you need this: Covers your total loop length with the calculated roll size.
PEX Tubing
2
1-Port Stainless Steel Hydronic Manifold
1-port manifold with flow meters and balancing valves to match 1 loop.
Why you need this: One port per calculated loop.
Manifold
3
Thermostatic Mixing Valve
Temps the supply water for radiant loops. Sized for 0.4 GPM flow rate.
Why you need this: Keeps supply water at a safe floor temperature.
Mixing Valve
4
Circulator Pump
Matched to 0.4 GPM total system flow. Choose a variable-speed ECM pump for zone efficiency.
Why you need this: Moves the calculated GPM through the loops.
Circulator Pump
5
PEX Foamboard Staples / Clips
Secures PEX to insulation foamboard at 8" spacing during slab/pour installation.
Why you need this: Holds tubing at your calculated spacing.
Fasteners
6
PEX Crimping / Expansion Tool Kit
Complete tool kit for 1/2" PEX connections (crimp or expansion per your fitting type).
Why you need this: Makes the manifold and loop connections.
Tools
7
Programmable Hydronic Thermostat + Zone Actuators
1 zone thermostat with matching actuator for manifold ports.
Why you need this: Zone control for each room.
Thermostat

What this heat-loss calculator does

This tool estimates room-by-room heating load for a US radiant floor so you can size a boiler, heat pump, or circulator in planning terms. Enter each room’s net area and insulation level, or a custom BTU/sq ft. The calculator multiplies net area by that factor, sums the rooms, and converts the total load to GPM at your chosen ΔT.

The formula

BTU/hr = net sq ft × BTU/sq ft. The built-in factors are 20 for well insulated, 28 for average, and 35 for poor insulation or a demanding slab. GPM = BTU/hr ÷ (500 × ΔT). These are planning rules of thumb, not a full Manual J. If you have a professional heat-loss report, use the custom BTU/sq ft field.

Worked example

A 1,000 sq ft net area at average 28 BTU/sq ft is 28,000 BTU/hr. At a 20°F ΔT the calculator reports 2.8 GPM. At a 15°F ΔT the unrounded result is 3.73 GPM, which the tool displays as 3.7 GPM. Loop count is a separate calculation from tubing length; changing ΔT changes flow, not the number of loops.

See how to calculate GPM for a radiant floor for the flow formula, and how to size a hydronic manifold to connect load, ports, and loop balance. Confirm the equipment selection with a licensed HVAC professional.

As an Amazon Associate I earn from qualifying purchases.

Frequently asked questions

How is BTU/hr estimated?
Net heated area is multiplied by 20, 28, or 35 BTU/sq ft, or by a custom value you enter from a heat-loss report.
What GPM does 1,000 sq ft at 28 BTU/sq ft need?
28,000 BTU/hr is 2.8 GPM at a 20°F ΔT and 3.7 GPM at a 15°F ΔT in the calculator.
Does this replace a Manual J heat loss?
No. It is a planning estimate for US homeowners. Use a professional room-by-room heat loss when you need a final equipment size.
Why didn’t GPM change my loop count?
Loops come from PEX length and the maximum circuit length. GPM comes from load and ΔT. Both are required, but they are different calculations.